Overview

1-7

Overview of Setting Up the Adapter

To set up the Enhanced DeviceNet adapter, you must perform the
following tasks:

1. Install the module or mount the board. Refer to Chapter 2,

Installation.

2. Set the adapter’s node address and configure the adapter’s

parameters. Refer to the following table:

3. Configure a scanner (either PLC or SLC) to communicate with

the Adapter. Refer to Chapter 5, Configuring a Scanner to
Communicate with the Adapter
.

4. If necessary, create a ladder logic program to control the

SCANport product. Refer to Chapter 6, Ladder Logic
Programming
.

Required Tools and Equipment

The tools and equipment required, depend on if you are using a
1203-GU6 module or 1336-GM6 board.

1203-GU6 Module

To install and configure a 1203-GU6 module, you need the following:

Enhanced DeviceNet communications module (1203-GU6).

5-pin or 10-pin plug-in connector (supplied with module).

35 x 7.5 mm DIN rail A (Allen-Bradley part number 199-DR1;
46277-3; EN 50022).

1/8" flathead screwdriver.

Appropriate cables for SCANport and DeviceNet connections.
Refer to the Selecting Cables section in Chapter 2, Installation.

A 1203-SFC serial cable.

A PC running either a Windows terminal emulation program
(e.g., HyperTerminal) or a VT100-compatible terminal.

If using:

Then refer to:

1203-GU6 module’s serial connection

Chapter 3,

Configuring the 1203-GU6

Enhanced DeviceNet Module Using a
Serial Connection

1203-GU6 module’s DeviceNet connection

Chapter 4,

Configuring the Enhanced

DeviceNet Adapter Using RSNetWorx for
DeviceNet

1336-GM board

Chapter 4,

Configuring the Enhanced

DeviceNet Adapter Using RSNetWorx for
DeviceNet