Chapter

3

Configuring the 1203-GU6 Enhanced
DeviceNet Module Using a Serial
Connection

Chapter Objectives

Chapter 3 provides information that you need to configure the
1203-GU6 module using a serial connection. In this chapter, you will
read about the following:

Factory-default settings for the module.

Equipment necessary to make a serial connection to the
1203-GU6 module.

Connecting either a PC running terminal emulation software or
VT100-compatible terminal to the 1203-GU6 module.

Using HyperTerminal to configure or edit the module’s
parameters, display its event queue, view its I/O data, view DF-1
statistics or serial number, and perform a flash upgrade.

Important: DriveExplorer™ can also be used to configure the
adapter via its serial port. Refer to the DriveExplorer documentation
from more information. To configure a 1203-GU6 module over the
DeviceNet network or to configure a 1336-GM6 board, refer to
Chapter 4, Configuring the Enhanced DeviceNet Adapter Using
RSNetWorx for DeviceNet.

Factory Default Settings for the
1203-GU6 Module

The factory-default settings of the Enhanced DeviceNet adapter
include the following:

16-bit Logic Command/Status enabled for polling.

16-bit Reference/Feedback enabled for polling.

If the scanner is put into program mode or the network fails, the
SCANport product will be faulted by the module.

A node address of 63.

DeviceNet autobaud detection enabled.

Serial baud rate of 9600.