3-8

Configuring the 1203-GU6 Enhanced DeviceNet Module Using a Serial Connection

Using a VT100-Compatible Terminal

The following instructions describe how to establish a serial
connection to the module using a VT100-compatible terminal.

1. Connect a 1203-SFC serial cable to your terminal and then to the

serial port on the module. See Figure 3.1.

2. Start your terminal.

3. Select the following settings:

9600 in the Bits per second field.
If you’ve already set the module’s Serial Port Rate parameter
to enable 19200 bps, set the bps to 19200 in this field.

8 in the Data bits field.

None in the Parity field.

1 in the Stop bits field.

None in the Flow Control field.

4. Press the Enter key. The main menu of the Enhanced DeviceNet

application appears.

Figure 3.8

Main Menu