Configuring the 1203-GU6 Enhanced DeviceNet Module Using a Serial Connection

3-11

2. Press 2 to select 2> Display Event Queue. The event queue

appears.

Figure 3.10

The Event Queue

3. Scroll through the list of Event Queue parameters by pressing the

Up Arrow or Down Arrow key. Refer to Appendix G, Event
Queue Messages
, for a list of faults.

4. If desired, clear the current fault in the adapter by setting Clr

Event Queue (1) to Enable and pressing the Enter key.

Important: The Fault is cleared in the module and a “Clear Fault”
event is added to the Event Queue.

5. Press the Escape key to return to the main menu.

Number

Name

Description

1

Clr Event Queue

Enable = Clears the event queue.
Ready = Leaves the event queue as is.

2 – 7

Event Queue 1 — Event Queue 6

Event in the event queue. Most recent event is listed in Event Queue 1.

8

Flash Upgrades

Number of times the adapter has been flash upgraded.