Enhanced DeviceNet Adapter’s Parameters

Using Master-Slave
Communications

To have your Enhanced DeviceNet adapter receive its I/O from a
scanner (PLC or SLC) on the DeviceNet network, you must configure
it for Master-Slave communications.

Figure B.2

Master-Slave Communications

Master-Slave communications let you transmit 2 – 10 words of I/O
data between the adapter and the scanner.

How you configure your adapter and scanner depends on the type of
allocation you are using. The adapter supports the following:

Polled.

COS (Change of State).

Cyclic.

Polled and COS.

Polled and Cyclic.

Polled Allocation

In polling, the scanner sends control data to the adapter, and then the
adapter responds with its status data. To use polling, you must enable
polling in the adapter and in the scanner.

1. Enable the desired I/O and datalinks (parameters 4 – 8).

2. Set the M-S Input (24) parameter. Refer to the “M-S Input

Parameter Configurations” section in this chapter.

3. Set the M-S Output (25) parameter. Refer to the “M-S Output

Adapter Input

Adapter Output

Master Data from

DeviceNet

Slave Data to

DeviceNet

Data from the

SCANport

Device

Data to the

SCANport

Device

Logic Command

Reference

DL A1 Inp

DL B1 Inp

DL C1 Inp

DL D1 Inp

DL D2 Inp

DL C2 Inp

DL B2 Inp

DL A2 Inp

Logic Status

Feedback

DL A1 Out

DL B1 Out

DL C1 Out

DL D1 Out

DL D2 Out

DL C2 Out

DL B2 Out

DL A2 Out

M-S Output (25)

MSB

1=Enable
0=Disable

LSB

X

X

X

M-S Input (24)

MSB

LSB

X

X

X