Performing a flash upgrade to the module, Performing a flash upgrade to the module -15, Specifications – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 45

Advertising
background image

Configuring the 1203-GU6 Enhanced DeviceNet Module Using a Serial Connection

3-15

Performing a Flash Upgrade to the
Module

You can upgrade the Enhanced DeviceNet adapter’s firmware using
the module’s serial port. To ensure a successful flash, we recommend
the following:

If using a laptop, turn off the FIFO buffers in HyperTerminal. In
Windows 95, select File and then Properties. In the Properties
dialog box, click Configure and then click Advanced. Uncheck
Use FIFO buffers.

Flash the upgrade file from a local hard disk (not a network drive
or floppy disk).

Run only your terminal emulation software while performing the
flash.

Disable the screen saver.

Important: To perform a flash upgrade to your module’s firmware
through the serial port, you must use a PC running terminal emulation
software that supports an X-modem CRC binary transfer.

Important: When you request a flash upgrade, the SCANport
product may fault and stop. To exit the flash upgrade option before
the download has completed, simultaneously press the Control and X
keys.

To perform a flash upgrade, you need to:

1. Establish a serial connection to access the module’s software.

Refer to the “Establishing a Serial Connection to the Module”
section earlier in this chapter.

2. Obtain the software file that contains the upgrade and record its

location. Note the firmware/revision number above the Main
Menu options in order to verify the upgrade later.