Displaying and clearing the module’s event queue – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 40

Advertising
background image

3-10

Configuring the 1203-GU6 Enhanced DeviceNet Module Using a Serial Connection

2. Press 1 to select 1> Edit Setup Parameters. The first parameter

appears on the bottom of the screen.

Figure 3.9

Edit Parameters

3. If necessary, scroll through the list of parameters by pressing the

Up arrow key or Down arrow key.

4. Edit parameters as necessary using the left arrow and right

arrow keys. Refer to the “Navigation Techniques” section earlier
in this chapter for information on changing parameter values.
Refer to Appendix B, Enhanced DeviceNet Adapter’s
Parameters, for acceptable values for each parameter.

5. If necessary, reset the module by enabling the Reset Adapter

parameter (22). Refer to Appendix B, Enhanced DeviceNet
Adapter’s Parameters, to see if the parameter you changed
requires the module to be reset in order to take effect.

Displaying and Clearing the
Module’s Event Queue

If an unexpected problem occurs with the module, you may need to
check the event queue to view events that have happened in the
module. Follow these instructions:

1. Establish a serial connection to access the module’s software.

Refer to the “Establishing a Serial Connection to the Module”
section earlier in this chapter.