8-3

SCANport Status LED States

The LED furthest from the DeviceNet connector is the SCANport
Status LED, and is labeled “SP.” It indicates the status of the
SCANport connection, and functions as follows:

LED Viewed:

If:

State:

Indicates

Action:

SCANport

Status LED

LED is off

Not powered

No power

Ensure that the connected SCANport device is powered
and that the product is connected to the adapter.

LED is flashing
green

Online/ I/O
connecting

Requesting I/O
connections or no I/O
is selected

No action needed. Adapter is establishing one or more of
the I/O connections with the SCANport device.

LED is steady green

I/O operational

One or more
connections
established

No action needed.

LED is flashing red

Configuration fault

SCANport problem:
No communications
seen from the
SCANport device to
request connections

1. Reseat cable properly.
2. Replace cable.

LED is steady red

Link failure

SCANport failure:
Poor cable connection
does not allow proper
port identification or
the SCANport device
isn’t allowing the
configured I/O
connections.

1. Check all SCANport cables and connections to the
SCANport device.
2. Ensure datalinks are not enabled on a product that
doesn’t support datalinks. Or, ensure that a particular
datalink is not already being used by another adapter on
the same SCANport device.

In either case, the adapter must be properly configured
and power cycled after the problem is fixed.

LED is steady
orange

Failed SCANport
compatibility test

Call Rockwell Automation support.