Enhanced DeviceNet Adapter’s Parameters

Enhanced DeviceNet Adapter
Parameters

The following table provides information on the Enhanced DeviceNet
communications adapter’s parameter set.

Important:

When accessing this parameter set

through the

DeviceNet Parameter Class, add

the adapter’s parameter number

to

the number of the last parameter of the SCANport device.

When

accessing this parameter set

through the vendor-specific SCANport

Variables-Linear Class, add the adapter’s parameter number to
4000H.

#

Name

Valid Values/

Settings

Default

Writable

Reset or

Power Cycle

Description

1

SCANport

Adapter

0-7

NA

No

No

Identifies the port number to-which the adapter
is connected on the SCANport product.

2

DN Node Address

0-63

63

Yes

Yes

Identifies the DeviceNet Node Address for the
adapter.

3

DN Data Rate

125K
250K
500K

Auto

Auto

Yes

Yes

Identifies the data rate used on the DeviceNet
network.
Important: At least one node on your
DeviceNet network must be configured to a
data rate (125, 250, or 500 K), not autobaud.

4

Cmd/Stat Config

Off, On

On

Yes

Yes

Determines whether to pass logic command and
analog reference control data from a DeviceNet
connection to a SCANport product. If you are
using a Master (scanner), parameters 24 and 25
must also be set.

5

Datalink A Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink A from a DeviceNet
connection to the SCANport product. If you are
using a Master (scanner), parameters 24 and 25
must also be set.

6

Datalink B Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink B from a DeviceNet
connection to the SCANport product. If you are
using a Master (scanner), parameters 24 and 25
must also be set.

7

Datalink C Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink C from a DeviceNet
connection to the SCANport product. If you are
using a Master (scanner), parameters 24 and 25
must also be set.

8

Datalink D Cfg

Off, On

Off

Yes

Yes

Determines whether to pass control data
contained in datalink D from a DeviceNet
connection to the SCANport product. If you are
using a Master (scanner), parameters 24 and 25
must also be set.

Important: For information on accessing and editing parameters, refer to Chapter 3, Configuring the 1203-GU6 Using a Serial
Connection
, or Chapter 4, Configuring the 1203-GU6 or 1336-GM6 Adapter Using RSNetWorx for DeviceNet.