Publication GMSI10-UM014D-EN-P - May 2010

DeviceNet Objects 109

Instances

There are 9 instances of this object. Each instance is permanently associated
with a different measurement.

Instance Attributes

Table C.27 Alarm Object Instances

Instance Number

Associated Measurement

1

CH 1 Shaft Relative Overall

2

CH 2 Case Absolute Overall

3

CH 1 DC Bias

4

CH 2 DC Bias

5

CH 1 Shaft Relative 1X Magnitude

6

CH 2 Case Absolute 1X Magnitude

7

Shaft Absolute Overall

8

Shaft Absolute 1X Magnitude

9

Speed

Table C.28 Alarm Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Alarm Status

3 BITS

The current status of the
alarm.

0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault

4

Get/Set

Alarm Enable

BOOL

Indicates whether this
alarm object is enabled.

0 = Disabled
1 = Enabled

6

Get

Threshold Units

USINT

Indicates whether the
threshold and hysteresis
value are specified in
units of measure or
percentage of full scale.

Set to 1
1 = Measurement units

7

Get/Set

Condition

USINT

Indicates on which side of
the threshold values the
alarm and danger
conditions exist. Not
applicable to vector
alarms.

0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range