Publication GMSI10-UM014D-EN-P - May 2010

Installing the Absolute Shaft Module 29

Figure 2.17 Non-Contact Sensor and 9000 Series Sensor Wiring

Connecting Two Non-Contact Sensors and 9000 Series Sensor

The following figure shows the wiring of two non-contact sensors and a 9000
series sensor to the terminal base unit. One non-contact sensor must be wired
to channel 1 and the 9000 sensor must be wired to channel 2. The second
non-contact sensor is wired to the tachometer input signal.

IMPORTANT

Make certain the IEPE Power parameter for channel 2 is
enabled so power is provided to the 9000 sensor. Refer
to Channel Parameters on page 46.

TYPICAL WIRING FOR NON-CONTACT SENSOR AND 9000

SERIES SENSOR TO XM-121 ABSOLUTE SHAFT MODUL E

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

0

16

22

6

21

Channel 2 Input Signal

Signal Common

5

37

SIG

-24

COM

17

1

Signal Common

Channel 1 Input Signal

-24V DC

13

Shield

S hield Floating

Isolated Sensor Driver

*

*

*Note: Jumpering terminal 5 to terminal 21
configures CH 1 buffer (-24V to +9V)

Jumpering terminal 6 to terminal 22
configures CH 2 buffer (-5V to +24V)

IMPORTANT

The Absolute Shaft module requires the XM-121 module
revision B01 (and later). Earlier revisions of the module do
not support the Absolute Shaft wiring configuration.