Publication GMSI10-UM014D-EN-P - May 2010

46 Configuration Parameters

Channel Parameters

The channel parameters define the characteristics of the transducers you will
be using with the Absolute Shaft module. Use the parameters to configure the
transducer sensitivity, operating range, and power requirements. There are two
instances of the channel parameters, one for each channel.

The Absolute Shaft module requires the correct transducers.

Channel 1 must be connected to a non-contact probe measuring
acceleration in mils or µm.

Channel 2 must be connected to a 9000 series sensor measuring
acceleration or velocity in ips, mm/sec or g’s.

Channel Parameters

Parameter Name

Description

Values/Comments

Channel Name (XM Serial
Configuration Utility only)

A descriptive name to help identify the channel in
the XM Serial Configuration Utility.

Maximum 18 characters

Controls whether to provide standard accelerometer
(IEPE) power to the transducer (channel 2 only). Refer
to Connecting the Transducers on page 27 for wiring
requirements.

The type of case sensor wired to channel 2.

Options: 9100VO

9000A
9100CSA
9100T

Sensitivity

The sensitivity of the transducer in millivolts per
Eng. Unit.

The sensitivity value is included with
the transducer’s documentation or it
may be imprinted on the side of the
transducer.

Eng. Units

Defines the native units of the transducer. Your
choice controls the list of possible selections
available in the Output Data Units parameter. It
also affects other module parameters.

Fault Low

The minimum, or most negative, expected DC
voltage from the transducer.

Volts

Note: A voltage reading outside this
range constitutes a transducer fault.

Fault High

The maximum expected DC bias voltage from the
transducer.

XM Configuration
Utility

EDS File

Enable IEPE

IEPE Power

XM Configuration
Utility

EDS File

Check = Enable

Enabled

Clear = Disable

Disabled

XM Configuration
Utility

EDS File

Sensor

Case Sensor
Type

Channel Sensor

Eng. Unit
Options

1

------

mils
µm

2

9100 VO

ips
mm/s

9000A

g

9100 CSA g

9100 T

g