Tachometer Transducer Parameters

Tachometer Transducer Parameters

Parameter Name

Description

Values/Comments

Tachometer Name (XM Serial
Configuration Utility only)

A descriptive name to help identify the tachometer in
the XM Serial Configuration Utility software.

Maximum 18 characters

Fault Low

The minimum, or most negative, expected DC
voltage from the transducer.

Volts

Note: A voltage reading outside this
range constitutes a transducer fault.

Fault High

The maximum expected DC voltage from the
transducer.

DC Bias Time Constant

The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2 x

π

x DC Bias Time Constant). See

example table below.

Seconds

Time Constant

(seconds)

-3dB Frequency

(Hz)

Settling

(seconds)

1

0.159

2.2

2

0.080

4.4

3

0.053

6.6

4

0.040

8.8

5

0.032

11

6

0.027

13.2

7

0.023

15.4

8

0.020

17.6

9

0.018

19.8

10

0.016

22