Publication GMSI10-UM014D-EN-P - May 2010

136 Guidelines for Setting the Full Scale Value

XM-121 Absolute Shaft Full
Scale Tables

Use the following tables to help you determine the optimal Full Scale value for
the XM-121 Absolute Shaft module. Refer to the table that corresponds to the
units of vibration that will be used for monitoring.

At frequencies above 60 Hz, the maximum vibration level allowed is reduced.
Use the following formula to determine the maximum vibration level.

.

Table D.1 XM-121A Measuring Case Absolute with Accelerometer (100 mV/g)

Maximum Vibration Level

Full Scale Setting

Max High Frequency Peak Amplitude

mils pp

micrometers pp

0.8Hz HPF

2Hz HPF

4Hz HPF

23.8Hz HPF

(g pk)

5 125

0.0013

0.003

0.006

0.036

4

10

250

0.0026

0.006

0.012

0.072

4

20

500

0.007

0.02

0.04

0.24

4

50

12500

0.014

0.04

0.08

0.4

12

Table D.2 XM-121A Measuring Case Absolute with Velocimeter (100 mV/ips)

Maximum Vibration Level

Full Scale Setting

mils pp

micrometers pp

0.8Hz HPF

2Hz HPF

4Hz HPF

23.8Hz HPF

5

125

0.1

10

250

0.2

20

500

0.3

50

12500

1

Max Vibration Level (mils pp)

Max High Freq Peak Amplitude (g) 19530 freq^2

×

=

Table D.3 XM-121A Measuring Shaft Relative with Displacement Sensor (200 mV/mil)

Maximum Vibration Level

Full Scale Setting

mils pp

micrometers pp

0.8Hz HPF

2Hz HPF

4Hz HPF

23.8Hz HPF

5

125

1

10

250

2.5

15

375

4

20

500

5

50

12500

10