Waveform measurement parameters – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual

Page 58

Advertising
background image

Publication GMSI10-UM014D-EN-P - May 2010

50 Configuration Parameters

Waveform Measurement Parameters

Use the waveform measurement parameters to set up the waveform
measurements. The waveform measurement parameters apply to both
channels.

Overall Damping Factor

This parameter is used in conjunction with the
Overall Time Constant to vary the characteristics
of the response of the digital filter used in
calculating the Overall Value.

An overall value for a measurement with a damping
factor near 1.0 (critical damping) will slowly rise or
fall for the full settling time specified by the Overall
Time Constant
before reaching the final value. An
overall value for a measurement with a damping
factor near 0.707 will rise or fall quickly and may
"overshoot" (measure a value greater or less than the
final value) before reaching the final value for a
given input signal.

Enter a value from 0.707 to 1.0.

Overall Measurement Parameters

Parameter Name

Description

Values/Comments

Waveform Measurement Parameters

Parameter Name

Description

Values/Comments

Number of Points

The number of samples in the waveform
measurement.

Options: 256

512
1024
2048

Waveform Period

The total period of the waveform measurement.

Seconds

FMAX (Hz) (XM Serial
Configuration Utility only)

Displays the maximum frequency included in the
waveform measurement.

Advertising