Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual

Page 66

Advertising
background image

Publication GMSI10-UM014D-EN-P - May 2010

58 Configuration Parameters

Threshold Multiplier

The action to take when the setpoint multiplier
switch is closed (push button engaged or toggle
switch flipped to on) and during the startup period
once the switch is reopened. The module applies the
multiplier to the alarm thresholds during this time to
avoid false alarms at resonance frequencies.

Note: The multiplication may have the opposite of
the intended effect under certain circumstances. For
example, if the Condition is set to "Less Than" and
the thresholds are positive, then multiplication of the
threshold values increases the likelihood of the
measured value being within the alarm range.
Therefore, you may want to set Threshold
Multiplier
to zero to disable the alarm during the
startup period.

Enter any fractional value between 0
and 10.

Enter 0 (zero) to disabled the alarm
during the startup period.

Inhibit Tachometer Fault

Controls whether to inhibit the tachometer fault
during the startup period.

During startup, the machine may be turning very
slowly and cause the XM module to detect a
tachometer fault. The Alarm status will state that a
tachometer fault condition exists unless the
tachometer fault is inhibited.

Speed Range Enable

Controls whether the selected alarm is enabled only
when the measured speed is within a machine speed
range. Enter the machine speed range in Speed
Range High
and Speed Range Low.

Note: The tachometer must be
enabled (Pulses Per Revolution set
to 1 or more) and a tachometer signal
must be provided at the tachometer
input when Speed Range Enable is
enabled.

Speed Range Low

The lesser threshold of the machine speed range.
This value must be less than the Speed Range
High
value.

This parameter is not used when Speed Range
Enabled
is disabled.

RPM

Speed Range High

The greater threshold of the machine speed range.
This value must be greater than the Speed Range
Low
value.

This parameter is not used when Speed Range
Enabled
is disabled.

RPM

Alarm Parameters

Parameter Name

Description

Values/Comments

XM Configuration
Utility

EDS File

Check means inhibit
tachometer fault

Inhibit Tach
Fault

Clear means do not
inhibit tachometer
fault

Do not inhibit

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled