Instance attributes – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual

Page 137

Advertising
background image

Publication GMSI10-UM014D-EN-P - May 2010

DeviceNet Objects 129

Instance Attributes

Table C.54 Transducer Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

DC Bias

REAL

The measured average DC
bias of the transducer
signal in volts.

Volts

4

Get

Status

BOOL

Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).

0 = No fault
1 = A transducer fault exists

5

Get/Set

Sensitivity
Value

REAL

Value of the sensitivity of
the transducer in
millivolts per Sensitivity
Units
.

6

Get/Set

Sensitivity Units ENGUNIT

Units of the denominator
of the Sensitivity Value.

See DeviceNet Specification
Volume 1 Appendix K.

Valid values:
Channel 1
mils = 0800 hex
µm = 2204 hex

Channel 2
g =1504 hex
in/sec = 2B07 hex
mils = 0800 hex
mm/s = 0900 hex

Channel 3
Not applicable

7

Get/Set

Fault High

REAL

The maximum expected
DC Bias voltage from the
transducer in volts.

Volts

8

Get/Set

Fault Low

REAL

The minimum expected
DC Bias voltage from the
transducer in volts.

Volts

9

Get/Set

Power Type

USINT

Indicates the type of
power supplied to the
transducer.

0 = No power supplied
1 = Constant current (IEPE
accelerometer)

13

Get/Set

DC Bias Time
Constant

REAL

The time constant value
used for exponential
averaging of the DC Bias
value (a low pass
filter/output smoothing
filter).

Seconds