Services, Overall measurement object (class id 322h), Class attributes – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual

Page 124: Overall measurement object (class id 322

Advertising
background image

Publication GMSI10-UM014D-EN-P - May 2010

116 DeviceNet Objects

Setting the Device Mode attribute to "1" (RUN) is equivalent to executing the
Start service. Setting the Device Mode attribute to "2" (PROGRAM) is
equivalent to executing the Stop service.

Services

Overall Measurement
Object
(Class ID 322

H

)

The Overall Measurement Object models the measurement of the amplitude
of a signal including a wide frequency range.

Class Attributes

The Overall Measurement Object provides no class attributes.

Table C.36 Device Mode Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Return the value of a single
attribute.

10

h

Instance

Set_Attribute_Single

Set the value of a single
attribute.

07

h

Instance

Stop

Transitions from Run to the
Program state.

06

h

Instance

Start

Validate the device
configuration settings and
transition to the Run state if
OK.

05

h

Instance

Reset

Transition to the Power Up
state. Load the non-volatile
configuration and transition
to the Run state if saved
configuration restored.

16

h

Instance

Save

Validate the device
configuration settings if
necessary and save them to
non-volatile memory.

09

h

Instance

Delete

Delete the saved
configuration from
non-volatile memory.

15

h

Instance

Restore

Load the saved
configuration or the factory
default configuration from
non-volatile memory.

Advertising