Instances, Instance attributes, Instances instance attributes – Rockwell Automation 1440-VLF02-01RA XM-121 Absolute Shaft Module User Manual

Page 125

Advertising
background image

Publication GMSI10-UM014D-EN-P - May 2010

DeviceNet Objects 117

Instances

There are 3 instances of this object.

Instance Attributes

Table C.37 Overall Measurement Object Instances

Instance Description

1

Channel 1 Shaft Relative Overall

2

Channel 2 Case Absolute Overall

3

Shaft Absolute Overall

Table C.38 Overall Measurement Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Overall Value

REAL

Measured value

The output value of the
measurement performed by the
Overall Measurement Object on
the input signal. The result of
the measurement process
specified by Measurement is
converted to the units specified
by Data Units to produce the
Overall Value.

4

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults.
1 = Alarm of fault condition
exists. The Overall Value
attribute may not represent the
actual field value.

5

Get

Data Units

ENGUNIT

The units context of the
Overall Value attribute.

This setting is determined by the
Channel Object’s Output Data
Units
attribute (see page 112).

6

Get/Set

Measurement

1

USINT

The measurement (or
calculation) performed to
produce the Overall
Value
.

0 = RMS
1 = RMS peak
2 = RMS pk-to-pk
3 = Peak
4 = Peak-to-peak
5-255 Reserved

Advertising