Installation and Operation Handbook

6-12

2408 and 2404 Controller

The following parameters apply if the standard 8-segment programmer is to be configured.

PROG Programmer configuration Values

Meaning

PtyP Programmer type

nonE

Programmer disabled (

factory setting

)

1

8-segment programmer enabled

HbAc Holdback

SEG


ProG

Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.

Pwr.F Power fail recovery

cont

Continue from last setpoint (SP)

rmP.b

Ramp from PV to SP at last ramp rate

rSEt

Reset the program

Srvo Starting setpoint of a

to.PV

From the Process Value (PV)

program (Servo point)

to.SP

From the setpoint

The following parameters apply if a 16-segment programmer is to be configured.

PROG Programmer configuration Values

Meaning

PtyP Programmer type

nonE

Programmer disabled

1

Single program

4

Four programs

20

Twenty programs

HbAc Holdback

SEG


ProG

Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.

Pwr.F Power fail recovery

cont

Continue from last setpoint (SP)

rmP.b

Ramp from PV to SP at last ramp rate

rSEt

Reset the program

Srvo Starting setpoint of a

to.PV

From the Process Value (PV)

program (Servo point)

to.SP

From the setpoint

out

Programmable event
outputs

no

YES

Disabled
Enabled

SYNC Synchronisation of programs

of several programmers

no

YES

Disabled
Enabled