Installation and Operation Handbook

Configuration

2416 Controller

6-13

Name

Description

Values

Meaning

The following digital events appear after

SEnS’. Any one, or more, of the events can be

combined on to the output (see Fig. 6-2) by selecting

YES’ in the lower readout.

1 - - -

Alarm 1 active

YES / no (- - -) = alarm type (e.g. FSL).

2 - - -

Alarm 2 active

YES / no If an alarm has not been configured

3 - - -

Alarm 3 active

YES / no in ‘AL ConF’ list, then display will

4 - - -

Alarm 4 active

YES / no differ:- e.g. Alarm 1 = ‘AL 1’.

mAn

* Controller in manual mode

YES / no

Sbr

* Sensor break

YES / no

SPAn

* PV out of range

YES / no

Lbr

* Loop break

YES / no

Ld.F

* Load failure alarm

YES / no

tunE

* Tuning in progress

YES / no

dc.F

* Voltage output open circuit, or
mA output open circuit

YES / no

rmt.F

* PDS module connection or
remote input open circuit

YES / no

iP1.F * Input 1 fail (not usable on 2416) YES/no
nw.AL

* New Alarm has occurred

YES / no

End

* End of setpoint rate limit, or end
of program

YES / no

SYnc

* Program Synchronisation active

YES / no (Not available in 2416 - set to ‘no’)

PrG.n

* Programmer event output
active, where ‘n’ = event number
from 1 to 8. (Not available with
8-segment programmer.)

YES / no

* These alarms are always non-latching. Process alarms 1, 2, 3 and 4 are configurable as
alarm latching or non-latching, see the ‘

AL’ List








Figure 6-2 Combining several digital events on to one output

dIG

SEnS

nor

inv

Output

Module

Digital
Events

OR