Installation and Operation Handbook

Configuration

2416 Controller

6-9

Name

Description

Values

Meaning

SP

Setpoint configuration

nSP

Number of setpoints

2, 4, 16 Select number of setpoints available

rm.tr

Remote Tracking

OFF

Disable

trAc

Local setpoint tracks remote setpoint

m.tr

Manual Track

OFF

Disable

trAc

Local setpoint tracks PV when in manual

Pr.tr

Programmer Track

OFF

Disable

trAc

Local setpoint tracks programmer SP

rmP.U

Setpoint rate limit units

PSEc

Per second

Pmin

Per minute

PHr

Per hour

rmt

Remote setpoint configuration

nonE

Disable

SP

Remote setpoint

Loc.t

Remote setpoint + local trim

rmt.t

Remote trim + local setpoint

AL

Alarm configuration

Values

The controller contains four ‘soft’ alarms, (indication only)
which are configured in this list. Once configured, they
can be attached to a physical output in module positions

1A 2A

or

3A

.

AL1 Alarm 1 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL2 Alarm 2 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL3 Alarm 3 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL4 Alarm 4 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

(not if ‘

AL4’ = ‘rAt’)

no/YES








Table A - Alarm types

Value Alarm type
OFF No alarm
FSL PV Full scale low
FSH PV Full scale high
dEv PV Deviation band
dHi PV Deviation high
dLo PV Deviation low
LCr Load Current low
HCr Load Current high
FL2 Not usable on 2416
FH2 Not usable on 2416
LOP Working Output low
HOP Working Output high
LSP Working Setpoint low
HSP Working Setpoint high
rAt PV Rate of change

AL4 only

*

Alarm Modes

no’ means that the alarm will be non-latching.

YES’ means that the alarm will be latched, with

automatic resetting. Automatic resetting means that
if a reset is actioned before the alarm has cleared,
then it will automatically reset when it clears.

Evnt’ means that the alarm is used to trip

an external event. If this option is selected the
front panel alarm message will not appear.

mAn’ means that the alarm will be latched,

and can only be reset after it has first cleared
(called ‘manual reset mode’).