Installation and Operation Handbook

User Calibration

2408 and 2404 Controller

7-3

OFFSET CALIBRATION

Offset calibration is used to apply a single fixed offset over the full display range of the
controller.









To calibrate, proceed as follows:
1. Connect the input of the controller to the source device to which you wish to calibrate.
2. Set the source to the desired calibration value.
3. The controller will display the current measurement of the value.
4. If the displayed value is correct, then the controller is correctly calibrated and no further

action is necessary. If it is incorrect, then follow the steps shown below.

Select ‘

FuLL’ access level, as described in Chapter 3.

x 3

Input list header

Press

until you reach the input list header.

Press

until you reach the

CAL’ display.

Calibration type

FACt:

Factory

Calibration

USEr:

User

Calibration

Use

or

to select ‘

FACt’.

Selecting ‘

FACt’ reinstates the factory calibration and allows the

application of a single fixed offset.

Press

continued
on the next page

Displayed Value

Input

Factory Calibration

Fixed Offset

CAL

FACt