Technical Specification

Installation and Operation Handbook

C-2

2416 Controller

Alarms

Number of alarms

Four

Alarm types

Absolute high or low. Deviation band, deviation high, deviation
low. Rate of change

Alarm modes

Latching or non-latching. Blocking. Energised or de-energised in
alarm

Setpoint programming
Number of programs

One or four

Segments per
program

16

Event outputs

Up to two


Communications (all modules are isolated)
Modbus

®

RS232,2-wire,RS 485 and 4 wire RS485 modules

Baud rate

1200, 2400, 4800, 9600 and 19,200 baud

PDSIO

Slave input (isolated)

Remote setpoint input with holdback to master

Master output

Isolated from main PV. Retransmission of setpoint, process value
or output

General

Display

Dual, 4 digit x 7 segment LED. Up to two decimal places

Supply

85 to 264Vac, 48 to 62 Hz, 10 W max OR
24Vdc or ac -15%, +20%. 10W max

Operating ambient

0 to 55

o

C and 5 to 90% RH non-condensing

Storage temperature

-10 to +70

o

C

Panel sealing

IP65

Dimensions

48mm wide x 48mm high x 150mm deep

Weight 250g
EMC standards

EN50081-2 & EN 50082-2 generic standards for industrial
environments

Safety standards

Meets EN61010, installation category II (voltage transients must not
exceed 2.5kV), pollution degree 2

Atmospheres

Not suitable for use above 2000m or in explosive or corrosive
atmospheres. Electrically conductive pollution must be excluded
from the cabinet in which this controller is mounted