Configuration

Installation and Operation Handbook

6-20

2408 and 2404 Controller

Name

Description

Values Meaning

4A

Module 4 configuration

Note: This option is not available on controllers from 01 Jan-04

id

Identity of module installed

HCS

High Current Switch

Func

Function

nonE Function disabled

dIG

Digital output function

HEAt Heating output

COOL Cooling output

VAL.L

% PID demand signal giving
minimum output

− ‘Out.L’

VAL.H

% PID demand signal giving
maximum output

− ‘Out.H’

Out.L

Minimum electrical output

Out.H

Maximum electrical output

SEnS

Sense of output

(Only if

Func’ = ‘dIG’)

nor

Normal (output energises when
TRUE, e.g. program events)

inv

Inverted (output de-energises
when TRUE, e.g. alarms)

When

SEnS’ appears, then further parameters are available.

These are identical to those in the

AA ConF’ list on Page 6-14.

Cust

8-point Custom Linearisation

(1)

in 1

Custom input 1

VAL.1

Linearisation Value representing

in 1

in 8

Custom

input

8

VAL.8

Linearisation Value representing

in 8

VAL.L

Out.H

Out.L

VAL.H

PID Demand Signal

Electrical
Output

Note:

1. Custom Linearisation is only available when ‘

3a-Conf’ or iP- ConF list has

inpt’ set to ‘mV.C’, or ‘mA.C’, or ‘V.C’.

2. The values and inputs must be continuously increasing or decreasing

VAL.1

VAL.3

in 8

in 1

in 3

VAL.8

Displayed Value

Electrical
Input