Thermcraft XST-3-0-36-3V User Manual

Page 115

Advertising
background image

Installation and Operation Handbook

Configuration

2408 and 2404 Controller

6-17

Name

Description

Values

Meaning

1A/b/C

(1)

Module 1 configuration

id

Identity of module installed

nonE

Module not fitted

rELy

Relay output

dC.OP

DC output isolated and non-
isolated

(1) If a dual-, or triple-, channel

LoG

Logic/PDS output

module is installed then the list

LoG.i

Logic input

headers

1b and 1C also appear

SSr

Triac output

dc.rE

DC retransmission (isolated)

dc.OP

Isolated DC output

SG.SU

Transducer power supply

For ‘

id’ = ‘rELy’, ‘LoG’, or ‘SSr’ use this parameter table:

Func

nonE

Function disabled

dIG

Digital output function

HEAt

Heating output

COOL

Cooling output

up

Open motorised valve

Function
(Only Channels

1A and 1C can be

Heating, or Cooling).
If a single logic output module is
fitted (code LO) this function will
need to be configured.

dwn

Close motorised valve

(Only if

id’ = ‘LoG’) SSr.1

PDS mode 1 heating

(Only if

id’ = ‘LoG’) SSr.2

PDS mode 2 heating

VAL.L

% PID demand signal giving
minimum output

− ‘Out.L’

VAL.H

% PID demand signal giving
maximum output

− ‘Out.H’

Out.L

Minimum average power

Out.H

Maximum average power

SEnS

Sense of output

(Only if

Func’ = ‘dIG’)

nor

Normal (output energises
when TRUE, e.g program
events)

inv

Inverted (output de-energises
when TRUE, e.g. alarms)

Notes:

1. When

SEnS’ appears, then further parameters are available. These are identical

to those in the

AA ConF’ list on Page 6-14.

2. If a Tranducer Power Supply is fitted, the

SenS

parameter selects the output

voltage.

nor

= 5V,

inv

= 10V

3.

A Transducer Power Supply does not provide any calibration facility and is simply
a 5 or 10V power supply.

4. To invert a PID output, the Val. H can be set below the Val.L

f

VAL.L

Out.H

Out.L

VAL.H

PID Demand Signal

Electrical
Output