2416 Controller

Name

Description



Atun Autotune list
tunE One-shot autotune enable
drA

Adaptive tune enable

drA.t Adaptive tune trigger level in

display units. Range = 1 to 9999

Adc

Automatic Droop Compensation
(PD control only)



Pid

PID list

G.SP

If Gain Scheduling has been
enabled (see Chapter 4), this
parameter sets the PV below
which ‘

Pid.1’ is active and above

which ‘

Pid.2’ is active.

SEt

Pid.1’ or ‘Pid.2’ selected

Pb

Proportional Band (

SEt 1)

(in display units)

ti

Integral Time in secs (

SEt 1)

td

Derivative Time in secs (

SEt 1)

rES

Manual Reset (%) (

SEt 1)

Hcb

Cutback High (

SEt 1)

Lcb

Cutback Low (

SEt 1)

rEL.C

Relative Cool Gain (

SEt 1)

Pb2

Proportional Band (

SEt 2)

ti2

Integral Time in secs (

SEt 2)

td2

Derivative Time in secs (

SEt 2)

rES.2

Manual Reset (%) (

SEt 2)

Hcb2

Cutback High (

SEt 2)

Lcb2

Cutback Low (

SEt 2)

rEL.2

Relative Cool Gain (

SEt 2)

The following three parameters are used for
cascade control. If this facility is not being
used, then they can be ignored.

FF.Pb

SP, or PV, feedforward propband

FF.tr

Feedforward trim %

FF.dv

PID feedforward limits

± %

Name

Description


mtr

Motor list - see Table 4-3

tm

Valve travel time in seconds

In.t

Valve inertia time in secs

bAc.t

Valve backlash time in secs

mp.t

Minimum ON time of output pulse

U.br

Not available in 2416





SP

Setpoint list

SSEL Select

SP 1 to SP16, depending

on configuration

L-r Local

(

Loc) or remote (rmt)

setpoint select

SP 1

Setpoint one value

SP 2

Setpoint two value

rm.SP

Remote setpoint value

rmt.t

Remote setpoint trim

rat

Ratio setpoint

Loc.t

Local setpoint trim

SP L

Setpoint 1 low limit

SP H

Setpoint 1 high limit

SP2.L

Setpoint 2 low limit

SP2.H

Setpoint 2 high limit

Loc.L Local trim low

Theses
parameters only
appear if
PDSIO is fitted

Loc.H Local trim high and Loc.t

(remote setpoint
+ local trim) in
SP Config list is
selected

SPrr

Setpoint Rate Limit

Hb.ty

Holdback Type for setpoint rate
limit (

OFF, Lo, Hi, or bAnd)

Hb

Holdback Value for setpoint rate
limit in display units. (

Hb.ty ≠

Off)