Load Current Monitoring and Diagnostics Installation and Operation Handbook

D-12 2408 and 2404 Controller

THE SCALING FACTOR

The value of the current displayed on the controller is scaled using the scaling factor. This is
found in the

inSt ConF list. It is set, by default, to 100 and assumes a single turn

through the current transformer. If two turns are made through the current transformer it will
be necessary to adjust the scaling factor to 50 to obtain the same reading.
Under normal conditions you should not need to change the scaling factor.
If, however, you wish to change the sensitivity of the current reading, for example, to read
very low currents you may need to change the number of turns through the PDCTX and/or
adjust the scaling factor to compensate. See also note 1 below.

TO ADJUST THE SCALING FACTOR

Do This

This Is The Display You Should See

Additional Notes

Press

button

until

inSt Conf is

displayed


Press

until

LC.Hi is displayed


Press

or

to change the
scaling factor










Note 1:-
Minimum Resolvable Current
TE10

4A RMS. It is not possible to read currents lower than 4A when using a TE10.

PDCTX 4A RMS for a single turn through the PDCTX
Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase the
number of turns through the PDCTX and adjust the scaling factor to compensate.
For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to
25 as shown in the table below.

Scalar = 100/N Where N = Turns through PDCTX

N

Scalar

N

Scalar

1 100

5 20

2 50 10 10
4 25

Maximum Resolvable Current
TE10

Determined by the maximum range of the SSR

PDCTX 100A (or 100 ampere turns)

Finally Exit configuration level. See Chapter 5.