Ip1.l – Thermcraft XST-3-0-36-3V User Manual

Page 253

Advertising
background image

Installation and Operation Handbook

User Calibration

2416 Controller

7-7

Select High-point Calibration

This is the Calibration Status display, again.

Use

/

to select the parameter for the High-point Calibration

of Input 1, ‘

ip1.H’.

Press

Adjust High-point Calibration

This is the display for adjusting the High Calibration point of
Input 1. The lower readout is a live reading of the process value,
which changes as the input changes.

Feed the desired high-point calibration signal to the controller,
from the calibration source. If the lower readout does not show
this value, then use

/

to adjust the reading to the required

value.

Press

to return to the ‘

ip-List’ header.



To protect the calibration against unauthorised adjustment return
to Operator level and make sure that the calibration parameters are
hidden. Parameters are hidden using the ‘

Edit’ facility

described in Chapter 3.

Adj

1200

CAL

ip1.L