Installation

Installation and Operation Handbook

1-18

2408 and 2404 Controller

MOTORISED VALVE CONNECTIONS

Motorised valves will normally be wired either to dual relay, or dual triac, output modules
installed in the Module 1 position, or to single channel relay and triac outputs installed in
Module positions 1 and 2. In the latter case, the convention is to configure output 1 as the
raise output and output 2 as the lower output.
Depending on the configuration, control of the valve is achieved in one of three ways:
1. With no position feedback potentiometer.
2. With a feedback potentiometer used to monitor the valve’s position. It does not

influence the control.

3. With a feedback potentiometer, where the valve’s position is controlled in response to the

signal from it.


Fig 1-11 Motorised valve connections

N

L

V+

VI

V-

Line

Neutral

Ground

+

+
PV

2D

2B

2A

2C

3D

3B

3A

3C

1D

1B

1A

1C

M

O

D

U

L

E

2

HF

HD

HE

C

O

M

M

S

1

JF

JD

JE

C

O

M

M

S

2

Common

Input 1

Input 2

85 to 264Vac

LC

LA

LB

AC

AA

AB

Alarm
relay

Motor supply

Motorised

valve

R

A

I

S

E

L

O

W

E

R

Dual

relay, or

triac,

output

module

RTD/Pt100

HB

HA

HC

Motor

Feedback

Potentiometer

(Optional)

+

Pot

Input

Module