Installation and Operation Handbook

Installation

2416 Controller

1-7

Module type

Terminal identity

Possible functions

A

B

Relay: 2-pin

(2A, 264 Vac max.)

Heating, Cooling, or Alarm output
Program event output
Valve raise or lower

Logic: non-isolated

(18Vdc at 20mA)

+

Heating, Cooling, or Alarm output
PDSIO mode 1,
PDSIO mode 2,
Program event

Triac

(1A, 30 to 264Vac)

Heating, Cooling,
Program event
Valve raise or lower

DC control: non-isolated

(10Vdc, 20mA max.)

+

Heating, Cooling.
Retransmission of PV, setpoint or
control output

Table 1-1 Module 1, 2 and 3 connections

To check which modules are installed in your particular controller, and which functions they
are configured to perform, refer to the ordering code and the wiring information on the
controller side labels.

1.2.4 Communications

module

The Communications module position will accept any of the modules listed in Table 1-2
below.
The serial communications can be configured for either Modbus, or EI bisynch protocol.

Communications module

Terminal identity (COMMS)

Module type

HA

HB

HC

HD

HE

HF

2-wire EIA-485 serial
communications

Common A

(+) B (

−)

EIA-232 serial
communications

Common Rx

Tx

4-wire EIA-485 serial
communications

A

(Rx+)

B

(Rx

−)

Common

A

(Tx+)

B

(Tx

−)

PDSIO Setpoint
retransmission

Signal Common

PDSIO remote setpoint input

--

--

--

--

Signal Common

Table 1-2 Communications connections

Line

Load