Screw spline & shear block systems installation, Systems installation, Screw spline and shear block – EFCO 403 Series Storefront User Manual

Page 65: Fig. # 67, Step 3) step 4), Fig. # 66, Step 1) step 2) fig. # 65

Advertising
background image

EFCO CORPORATION 1/2013 PART NO. Y001

Page 65 of 94

Series 401,402, & 403 Installation Instructions






























































Fig. # 67

STEP 2

STEP 3)

STEP 4)

OTHERS TYPICAL

Fig. # 66

9957 w/o CLIP SHOWN

BEAD OF SEALANT
JAMB TO JAMB

S

TYP. SILL

F098

sill flashing

Typical

SECTION IV C -

SYSTEMS INSTALLATION

The frame may be assembled as one unit before setting it in the opening.

STEP 1)

STEP 2)

Fig. # 65

DLO

DLO

DLO

CONTINUOUS FLASHING

F098

SCREW SPLINE AND SHEAR BLOCK

REF.

Install sill clips F098 (2 per DLO). Clips can only be used for units over

48 1/2" tall if less than a 1/2" caulk joint is used at the head. Units

must be tilted in as shown in Fig. # 65.

EFCO requires the use of perimeter adaptors located at the setting block
locations, typically at 1/4 points of the DLO. This is to prevent frame

distortion normally associated with large lites of glass. Also locate FS92
or FV58 at S401, FS93 or FV59 at S402, and FU99 or FV59 at S403 at
thru sill anchoring locations to prevent frame distortion. Refer to Fig. #
67 below.

Apply sealant to the upturned flashing leg at the horizontal cavity.

See Fig. # 67 below.

Tilt the unit and set it on the flashing, see Fig. # 66. Then stand the

unit up over the clips and proceed to anchor the unit in place.

Advertising