HI-3000 Series

6

Operation and Installation

Step 2. Push the up or down arrows until the cursor is next

to “OPTIONS”. (See Fig. 8)

FIG. 8: CONFIGURATION MENU/SELECTING

OPTIONS

Step 3. Press the Enter button. The Options submenu

appears with Remote I/O selected. (See Fig. 9)

Step 4. If the cursor is not in front of Remote I/O, push the

up arrow until the cursor is aligned with Remote I/
O.

Step 5. Press the Enter button. The Remote I/O Menu

appears. (See Fig. 10)

FIG. 9: OPTIONS/SELECTING REMOTE I/O

FIG. 10: REMOTE I/O MENU/SETTING

PARAMETERS

Step 6. Press the right or left arrow buttons to select the

Baud Rate. Left arrow decreases the rate and the
right arrow increases the rate. Baud Rate Selections
are:

57 kbaud

115 kbaud

230 kbaud.

Step 7. Press the Enter button to save the setting.
Step 8. Press the down arrow button until the cursor is in

front of Rack Address.

You can set the rack address in one of two
ways.

1.

Press on the clear button to clear the
existing value then use the alphanu-
meric keys to enter the address for this
module.

2.

Press on the right or left arrow buttons
to select the address.

Address Range - 0-59

Step 9. Press the Enter button to save the setting.
Step 10. Press the down arrow button until the cursor is in

front of Rack Size. (See Fig. 11)

FIG. 11: REMOTE I/O/SETTING RACK SIZE

Step 11. Press the right arrow button to select the rack size

of this module. The choices are:

1/4 quarter (Can start at 1,2,3,4)*

1/2 half (Can start at 1,2,3)*

3/4 three quarter (Can start at 1,2)*

FULL (Can start at 1)*

NOTE:

*The starting points are important when making
the starting quarter selection. For example you
can have a 1/4 rack start at quarter 1 and a 1/2
rack start at quarter 2.

Step 12. Press the Enter button to save the setting.
Step 13. Press the down arrow button until the cursor is in

front of Starting Quarter. (See Fig. 12)

FIG. 12: REMOTE I/O SELECTING STARTING

QUARTER

Step 14. Press the right or left arrow buttons to select the

starting quarter for this module. Keep in mind the
starting quarter requirements due to rack size.

>

OPTIONS
Remot e I/ O ON - >
Cont r ol Net I/ O OFF