FIG. 62: CONTROLNET CONFIGURATION/ENTER-

ING NODE ADDRESS

Step 8. Click on the Set Parameters button to save the set-

tings.

Step 9. Click on the left arrow or the word “home” at the

bottom of the page to return to the Home Page.

LED Status Indicators

The ControlNet Card is fitted with four bi-color status and
indicator LED’s. (See Fig. 88) During startup the Module
Status (LED 1) and the Module Owned (LED 4) are red for
one (1) second to indicate they are working properly. After
the one second period they are lit as specified below in the
tables. After the module is initialized, the network LED’s
will flash red/green for one (1) second, indicating a self test
of the network chip.

For information on setting up the module using RSLogix
5000 and RSNetworx go to the Network Section of this man-
ual.

EtherNet/IP™ Option Card Installation

CAUTION: M

AKE

SURE

THAT

YOU

USE

AN

ANTI

-

STATIC

STRAP

WHEN

INSTALLING

THE

E

THER

N

ET

/IP O

PTION

C

ARD

.

NOTE:

The dip switches do not function. It is a good idea
to leave all of them in the OFF position. Should
you accidentally turn on a dip switch nothing will
happen. The IP address is configured by the firm-

Color

Frequency

Description

Green

Flashing

Module is waiting for initialisation

Green

Steady on

Module is initialized

Red

Flashing

Minor fault, MacID has been changed
after initialisation, etc.

Red

Steady on

Major fault, module must be restarted

TABLE 4: LED 1 - MODULE STATUS

Color

Frequency

Description

Red/Green

-

See Table 5

TABLE 5: LED 2 - LED CHANNEL A

Color

Frequency

Description

Red/Green

-

See Table 5

TABLE 6: LED 3 - LED CHANNEL B

Color

Frequency

Description

Green

Steady on

A connection is opened against the
ControlNet Module

Off

-

No connection is opened

TABLE 7: LED 4 - MODULE OWNED

Channel LED’s

Description

A & B, steady off

Module is not initialized

A & B, steady red

Faulted unit, must be restarted or
repaired

A & B, alternating red/green

Selftest of bus controller

A&B, flashing red

Incorrect node configuration, dupli-
cate MacID, etc.

A or B, steady off

Channel is disabled, depending on
network configuration

A or B, steady green

Normal operation of channel

A or B, flashing green

Temporary errors (node will self cor-
rect) or node is not configured to go
online

A or B, flashing red

Media fault or no other nodes on the
network

A or B, flashing red/green

Incorrect network configuration

TABLE 8: CHANNEL LED’S