FIG. 49: CONTROLNET OPTION CARD INSTALLED

Removing the ControlNet Option Card

Step 1. Disconnect the BNC connectors or RS-45 connec-

tor.

Step 2. Use a phillips head screw driver and remove the

two (2) screws that fasten the ControlNet Option
Card panel to the HI 3000 Chassis.

Step 3. Using the thumb and index finger on both hands,

grasp the two (2) knobs on the card panel and pull
away from the instrument.

Step 4. When the ControlNet Option Card clears the chas-

sis, store in a static free, safe location.

ControlNet Connection and Setup

Hardware Requirements:

Hardy ControlNet Card.

ControlNet Cable with BNC Connectors
on both ends.

Software Requirements:

RSNetWorx™

RSLinx™

Hardy EDS File (Available on the HI 3000
CD or current EDS file can be downloaded
from Hardy Website.)

NOTE:

RSNetWorx™ and RSLinx ™ are trademarks of
Rockwell Software.

Four versions of Network Taps provide flexible mounting
options: "Y", "T", straight or 90° elbow (right angled).

FIG. 50: CONTROLNET CABLE ASSEMBLIES

Step 1. For normal operation connect the Cable to either

one of the BNC Connectors on the HI 3000 Con-
trolNet Card located at the rear panel of the HI 3000
Series module. (See Fig. 52)

NOTE:

Changing the rotary switches to an address other
than 0, 0 - ControlNet will not work. (See Fig. 51)

FIG. 51: ROTARY SWITCHES/SETTING NODE

ADDRESS TO 0, 0

Step 2. For redundant operation you need to connect to

both BNC connectors.

FIG. 52: REAR PANEL CONTROLNET CONNEC-

TORS AND LEDS

O 1

2

3

4 5

6

7

8

9

O 1

2

3

4 5

6

7

8

9