Te i/o configuration/selecting baud rate – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 21

Advertising
background image

7

Communications
Installation & Operation

Step 15. Press the Enter button to save the setting.
Step 16. Press the down arrow button until the cursor is in

front of Last Quarter.

Step 17. Press the right or left arrow buttons to toggle

between NO and YES. If the module is in the last
quarter select YES. If the module is not in the last
quarter select NO. Make sure you make the correct
selection each time.

Remote I/O Configuration Procedures from the
Web Page

Step 1. From the Home Page of the Instrument Click on

Configuration. (See Fig. 13) The Configuration
Options page appears. (See Fig. 14)

FIG. 13: INSTRUMENT HOME PAGE/SELECTING

CONFIGURATION

FIG. 14: CONFIGURATION - OPTIONS PAGE/

SELECTING VIEW REMOTE I/O CONFIGURATION

Step 2. Click on View Remote I/O Configuration. (See Fig.

14) The Remote I/O Configuration page appears.
(See Fig. 15)

FIG. 15: REMOTE I/O CONFIGURATION PAGE

Step 3. To select the Baud rate click on the Baud: pull

down menu. (See Fig. 16)

Step 4. Click on the Baud Rate you want to select. Baud

Rate Selections are:

57 kbaud

115 kbaud

230 kbaud.

NOTE:

If you only select one parameter (e.g. Address)
you need to click on set configuration to set the
entry. You do not need to select every category
before setting the configuration.

FIG. 16: REMOTE I/O CONFIGURATION/

SELECTING BAUD RATE

Step 5. To set the Node Address double Click in the

Address Field. Type in the Node Address of this
module.

Address Range - 0-59