Step 37. Click on the Select button. Net Weight/Channel 2

(HFI9) appears in the Current Mappings field to the
right of the Hardy Control-Link Float Out selection
(EFO6) (See Fig. 287).

FIG. 287: CURRENT MAPPINGS/GROSS WEIGHT/

CHANNEL 2 (HFI9) ASSIGNED TO HARDY

CONTROL-LINK FLOAT OUT/WORD 4 (EFO4)

Step 38. Click on the Map button to map the assignment

statement. (See Fig. 288)

FIG. 288: GROSS WEIGHT ASSIGNED TO HARDY

CONTROL-LINK FLOAT OUT

Step 39. You can continue this process up to Item FO62.
Step 40. To see what has been mapped click on the word

here in the statement “Click here for an expanded
map”. (See Fig. 289) The Expanded Map dialog
box appears. (See Fig. 290)

FIG. 289: SELECTING AN EXPANDED MAP

FIG. 290: EXPANDED MAP DIALOG BOX

Here is a table to show the mapping for the
OPC Server.

Configuring EtherNet/IP Using
RSLogix5000

®

These configurations procedures assume that

RSLogix5000

®

and ControlLogix5000

®

with an EtherNet/

IP™ module/bridge are set up and working correctly.

NOTE:

RSLogix5000® and ControlLogix5000® are reg-
istered trademarks of Rockwell Automation Inc.

NOTE:

The dip switches do not function. It is a good idea
to leave all of them in the OFF position.

Step 1. Create a new project or use an existing project and

set the program in “Offline” mode.

Step 2. Right click the EtherNet/IP module/bridge in the I/

O configuration. (See Fig. 291)

FIG. 291: I/O CONFIGURATION/ADDING A NEW

MODULE

Item #

Destination

Source

FO00

Hardy Control-
Link Float Output
- Word 0 (EFO0)

Gross Weight
Channel 1 (HFI4)

FO02

Hardy Control-
Link Float Output
- Word 2 (EFO2)

Net Weight Chan-
nel 1 (HFI8)

FO04

Hardy Control-
Link Float Output
- Word 4 (EFO4)

Gross Weight
Channel 2 (HFI5)

FO06

Hardy Control-
Link Float Output
- Word 6 (EFO6)

Net Weight Chan-
nel 2 (HFI9)