Chapter 2 - installation, About cable termination, Setting the cable termination dip switches – Hardy HI 2151/30WC Single-Scale Controller User Manual

Page 11: List of tables, Allation -1, Table 2-1 cable termination requirements -1, Table 3-1 interior dip swit, Table 3-2 ext, Table 3-3 bina

Advertising
background image

Chapter 2 - Installation

2-1

CHAPTER 2 - INSTALLATION

Remote I/O Board Cable
Termination Dip Switch
Configuration

About Cable
Termination

Weight controllers are connected to a cable in daisy-chain fashion and
are referred to as “nodes”. A Daisy Chain is a hardware configuration
in which devices are connected one to another in a series. The end
nodes on the daisy chain require termination resistors. The Remote I/O
board provides the S1 Dip Switches which are used for cable termina-
tion based on the baud rate. (See Table 2-1) The S1 Dip Switches are
only used on the last device in the daisy chain. For all other devices on
the daisy chain both dip switches should be set to OFF. (See Fig. 2)

NOTE:

Refer to your Allen-Bradley PLC-2, PLC-3, PLC-5 and SLC 500 manuals for the
maximum number of nodes available.

Setting the Cable
Termination Dip
Switches

Step 1.

For all RIO board options (except for the last device) make
sure the dip switches are set to the OFF position. (See Fig. 2-
1)

FIG. 2-1 REMOTE I/O S1 DIP SWITCH SETTINGS (DEFAULT)

NOTE:

The factory default setting is for both switches to be turned OFF. Also note that the
dip switches in Figure 2-1 have been rotated for illustration purposes.

BAUD

TERMINATION

MAX

NODES

MAX

LENGTH

SWITCH 1

SWITCH 2

57.6 K

150 Ohms

16

10,000 Feet

ON

OFF

115.2 K

150 Ohms

16

5,000 Feet

ON

OFF

230.4 K

82 Ohms

32

2,500 Feet

OFF

ON

TABLE 2-1: CABLE TERMINATION REQUIREMENTS

S1

ON

OFF

12

Advertising