Chapter 4 - Discrete Transfers

4-3

1 = Remote
Function Status
Byte

bit 0

Force display to Rate-of-Change mode

bit 1

Add current net weight to total

bit 2

Hold value on display

bit 3

Hold option card updates

bit 4

Force display to Net Weight mode

bit 5

Toggle lbs/kg

bit 6

Acquire Tare

bit 7

Print Request (RS232 and BCD ports)

2 = Indicator Group
2 Status Byte

bit 0

Weight currently displayed in pounds units

bit 1

Zero Track feature enabled

bit 2

Reserved for future use

bit 3

Current Gross Weight = 0

bit 4

Weight in motion, i.e. changing

bit 5

Gross Weight currently displayed

bit 6

Net Weight currently displayed

bit 7

Weight currently displayed in kilogram units

3 = Indicator Group
1 Status Byte

bit 0

Rate-of-Change currently displayed

bit 1

Setpoint Relay #2 active

bit 2

Setpoint Relay #1 active

bit 3

Peak Force (weight) currently displayed

bit 4

Totalized weight currently displayed

bit 5

Reserved

bit 6

Excitation Monitor Error

bit 7

Reserved

4 = Dipswitch
Settings (exterior)
Status Byte

bit 0

RE-calibrate toggle

bit 1

Option menu keypad lockout

bit 2

Setpoint menu keypad lockout

bit 3

Lb/Kg, Net/Gr, Tare, Zero keypad lockout

bit 4

Zero tracking enable

bit 5

Reserved for future use

bit 6

RS232 command lockout

bit 7

Multi-Drop enable

NOTE:

If Blind Mode dip switches status not visible.

NOTE:

The PLC will receive both words with each discrete read, but it is not guaranteed that
both words will be transferred as a unit. Both words will get transferred, but there
may be some delay between the two.

NOTE:

For the PLC-2

®

series, you must use a 1772-SD2 scanner and the PLC-2

®

system to

allow communication with the HI 2151WC via block transfer. Use block transfers
only.

NOTE:

For the SLC 5/02

®

or above processors, you must use a 1747-SN to allow communi-

cation with the HI 2151WC via discrete transfer. The 1747-SN does not support block
transfer.