Hardy HI 2151/30WC Single-Scale Controller User Manual

Page 36

Advertising
background image

HI 2151 SERIES WEIGHT CONTROLLERS REMOTE I/O OPTION

5-16

Block Write
Command Number
52: Downloading
Setpoint Relay
Parameters

BLOCK WRITE COMMAND NUMBER 52:Downloading Setpoint Relay Parameters

START

WORD DEFINITIONS:

#WORDS

WORD

Command number: A value of 52 (decimal)

bit 0

0

bit 1

0

bit 2

1

bit 3

0

bit 4

1

bit 5

1

bit 6

0

bit 7

0

bits 8 - 15

Reserved for future use

Setpoint Enable:

bit 8

Enable Relay #8 to evaluate weight

bit 9

Enable Relay #7 to evaluate weight

bit 10

Enable Relay #6 to evaluate weight

bit 11

Enable Relay #5 to evaluate weight

bit 12

Enable Relay #4 to evaluate weight

bit 13

Enable Relay #3 to evaluate weight

bit 14

Enable Relay #1 to evaluate weight*

bit 15

Enable Relay #2 to evaluate weight*

*Note: Notice relays 1 and 2 are not in numerical sequence

1

0

Force Relay Status*

bit 0

Turn relay #8 on regardless of weight (setpoint enable bit must be 0)

bit 1

Turn relay #7 on regardless of weight (setpoint enable bit must be 0)

bit 2

Turn relay #6 on regardless of weight (setpoint enable bit must be 0)

bit 3

Turn relay #5 on regardless of weight (setpoint enable bit must be 0)

bit 4

Turn relay #4 on regardless of weight (setpoint enable bit must be 0)

bit 5

Turn relay #3 on regardless of weight (setpoint enable bit must be 0)

bit 6

Turn relay #1 on regardless of weight (setpoint enable bit must be 0)

bit 7

Turn relay #2 on regardless of weight (setpoint enable bit must be 0)

*Note: Force relay on/off is only available over this interface. If you desire to manually set a relay to
trigger on a weight parameter, make sure force relay bit is set to 0.

1

1

bits 8 - 15

Setpoint description byte A (See Table 5-18 & 5-19)

bits 0 - 7

Setpoint description byte B (See Table 5-18 & 5-19)

1

2

bits 8 - 15

Setpoint description byte C (See Table 5-18 & 5-19)

Deadband value for setpoint #1
Deadband value for setpoint #2
Deadband value for setpoint #3
Deadband value for setpoint #4
Deadband value for setpoint #5
Deadband value for setpoint #6
Deadband value for setpoint #7
Deadband value for setpoint #8

2
2
2
2
2
2
2
2

3
5
7
9
11
13
15
17

Advertising