background image

II - SPECIFICATIONS

(cont.)

COMBUSTION SPECIFICATIONS

Item

Gas Type

Natural

Propane

Gas Consumption

Minimum Btu's

15,000

15,000

Maximum Btu's

199,000

199,000

Injector Diameter

Upper

ø.045 (1.15mm)

ø.029 (.75mm)

Inches (mm)

Lower

ø.070 (1.8mm)

ø.045 (1.15mm)

Main Burner

B3A7-1 (Lean and Rich Bunsen Burner)

Main Damper

H73-115 (Upper: ø6, Lower: Not Used)

Gas Pressure

Supply/Manifold

Minimum Supply

6" W.C.

10" W.C.

Maximum Supply

10.5" W.C.

13.5" W.C.

Low Fire Manifold

0.56" W.C.

0.88" W.C.

High Fire Manifold

3.4" W.C.

5.1" W.C.

11

Advertising
This manual is related to the following products: