LAARS IGE-199C-5(N,X) - Service Manual User Manual

Page 36

Advertising
background image

36

2) Is the flame rod normal? Error “72” is displayed

3) Is the water temperature thermistor normal?

Checking the flame rod.

a.

# Detach the flame rod terminal C1, and re-attempt

operation.

(“72 is displayed)

Proceed to check item 3 below.

(no “72” displayed)

Inspect flame rod wiring for current leak and inspect

flame rod for carbon build-up.

Measure resistance between the flame rod

Terminal C1 and the appliance earth.

Normal: 1 M Ω or more.

If normal, replace the PCB unit.

(Service Procedure IGE-2, page 47)

Faulty: Replace the flame rod.

See page 40 for additional information and resistance values

pertaining to the flame rod.

If error “32” is displayed, check the water

temperature thermistor.

a.

# Disconnect connector B5, and measure resistance of

the white ~ white wires.

Resistance > 1 M Ω = open circuit.

Resistance < 1 Ω = short circuit.

Normal: Proceed to check item 4 on the next page.

Faulty: Replace the water temperature thermistor.

(Service Procedure IGE-6, page 48)

See page 41 for additional information and

resistance readings pertaining to the

temperature themistor.

VI - TROUBLESHOOTING

(cont.)

BEFORE CARRYING OUT CHECKS MARKED WITH A # SIGN, DISCONNECT THE POWER SUPPLY.