LAARS IGE-199C-5(N,X) - Service Manual User Manual

Page 48

Advertising
background image

a.

Remove the four (4) Phillips screws that

secure the water inlet filter housing to the

unit. See picture below for location of

screws. Once screws are removed reach

into the unit and pull up and out on the

flow control assembly to remove it from

the appliance. Inspect o-ring for damage.

b.

Disconnect wiring harness from assembly

and remove the water flow control

assembly from the unit.

IGE - 4. Removal of Ignition Module:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

a.

Remove one (1) Phillips screw that secures

the sparker module to the unit casing.

b.

Disconnect high tension lead and

connector.

IGE - 5. Removal of the Combustion Fan:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

a.

Disconnect wiring harness from fan motor.

b.

Remove the (2) Phillips screws that secure

the combustion fan motor to the fan

housing. Pull the fan motor assembly

towards yourself to remove it.

IGE - 6. Removal of the Water Temperature

Thermistor:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

a.

Remove the two (2) Phillips screws that

secure the thermistor in place to remove

the water outlet temperature thermistor.

48