9) Is the change over solenoid (SV3) operating normally?

If error “11” or “71” is displayed, check the change over

solenoid (SV3).

a.

# Disconnect the changeover solenoid (SV3)

connector, and measure the resistance at the

solenoid terminals.

Normal: 1.7 – 2.1 K Ω

If normal, check b below.

Faulty: Replace the manifold assembly.

(Service Procedure IGE-8, page 49)

b.

Measure the voltage at the changeover solenoid

(SV3), brown – black wires.

Normal: 80 – 100 VDC

If normal, reconfirm gas pressures are correct.

Faulty: Replace the PCB unit.

(Service Procedure IGE-2, page 47)

VI - TROUBLESHOOTING

(cont.)

BEFORE CARRYING OUT CHECKS MARKED WITH A # SIGN, DISCONNECT THE POWER SUPPLY.