Vi - troubleshooting, Cont.) – LAARS IGE-199C-5(N,X) - Service Manual User Manual

Page 30

Advertising
background image

30

Nature of Fault

Examination

Point

Diagnostic Point

Values

Y/N

Action

Service

Procedure

2. Measure the voltage

at connector F with

appliance power supply

on.

F – Black ~ White

100 ~ 120 VAC

F

7

– Blue ~ Brown

100 ~ 120 VAC

Are values within

those specified at

left.

Yes

No

Go to A – (7)

Replace

transformer

IGE – 7

7. Check remotes (s)

(where connected.)

Measure voltage

between remote control

terminals at D.

11 ~ 13 VDC Digital

Yes

No

Check cable

for shorts or

broken wires.

Replace

remote

control.

Replace PCB.

IGE – 2

B. Digital monitor

lights up, but

combustion does

not commence.

(when remotes

are connected).

1. Check water flow

sensor.

1. Measure voltage

between red ~ black of
connector B

4

.

(See page 35)

2. Measure voltage

between yellow ~ black
at connector B

4

.

(See page 35)

11 ~ 13 VDC

4 ~ 7 VDC

Yes

No

Yes

No

Go to B–1-2

Replace PCB.

Go to B - 2

Replace water

flow sensor.

IGE – 2

IGE – 3

Error code "72"

displayed on the

digital monitor.

2. Check flame rod

# Measure resistance

between flame rod

terminal C

1

and earth.

(See page 36)

Resistance > 1MΩ?

Yes

No

Replace PCB

Replace flame

rod

IGE – 2

Error code "32"

displayed on the

digital monitor.

3. Check outgoing

water temperature

thermistor.

# Disconnect connector

B5 and measure

resistance.

Open circuit: > 1MΩ

Short circuit: < 1Ω

(See page 36)

Are values as shown

at left?

Yes

No

Replace water

temperature

thermistor.

Go to B - 4

IGE – 6

Error code "61"

displayed on the

digital monitor.

4. Check

combustion fan.

1. Check motor.

Measure voltage

between black ~ red at
connector A

1

.

(See page 37)

6 ~ 45 VDC (Fan on)
0 VDC (Fan off)

Yes

No

Go to B – 5-2

Replace PCB

IGE – 2

2. Check fan rotation

sensor. Measure voltage

between black ~ yellow
at connector A

1

.

(See page 37)

11 ~ 13 VDC

Yes

No

Go to B – 4-3

Replace PCB

IGE – 2

3. Measure voltage

between black ~ white

of connector A

1

.

(See page 37)

6 ~ 45 VDC

Yes

No

Go to B – 5

Replace fan

IGE – 5

VI - TROUBLESHOOTING

(cont.)

Troubleshooting Flow Chart

BEFORE CARRYING OUT CHECKS MARKED WITH

A # SIGN, DISCONNECT THE POWER SUPPLY.