VII - GAS PRESSURE SETTING PROCEDURE

All settings/adjustments must be performed

by a qualified Service Technician.

1.

Turn unit off at power source and turn off the gas to the water heater.

2.

Remove the front cover from the water heater.

3.

Remove the gas pressure test port plug. Connect manometer to this port. (See Figure #1 for

location of the test port plug.) Turn on the gas and power to the water heater.

4.

Flow water through the water heater at the maximum flow rate obtainable, at least three

gallons per minute.

5.

To adjust the "Low" fire pressure, use small (pocket) common screwdriver to set combustion

control dip switch #7 to the "ON" position, and switch #8 to the "OFF" position (see figure #2

for location of combustion control switches.) This will put the unit into forced low fire. Check

the pressure reading on your manometer. If the pressure needs adjusting, remove the rubber

plug from the bottom of the water heater casing (located beneath the regulator), to access the

regulator adjustment screw. Adjust the regulator screw to achieve the correct gas pressure.

(See figure #1 for location of the regulator adjustment screw.) Below are the proper pressures

for "Low" fire, per gas type.

Propane

0.88" w.c. @ 10" w.c. supply

(Low fire rate of 15,000 BTU's)

Natural

0.56" w.c. @ 6" w.c. supply

(Low fire rate of 15,000 BTU's)

6.

To adjust the "High" fire pressure, use small (pocket) common screwdriver to set combustion

control dip switch #7 to the "ON" position, and switch #8 to the "ON" position (see figure #2

for location of the combustion control switches), this will put the unit into forced high fire.

Check the pressure reading on your manometer. If the pressure needs adjusting, use small

(pocket) common screwdriver to adjust the high pressure "Pot". (See figure #2 for location of

"high pressure setting pot"). Below are the proper pressures for "High" fire.

Propane

5.1" w.c. @ 10" w.c. supply

(High fire rate of 199,000 BTU's)

Natural

3.4" w.c. @ 6" w.c. supply

(High fire rate of 199,000 BTU's)

7.

Verify both low and high fire pressures by placing the water heater into "Forced Low Fire" and

"Forced High Fire" as described in steps 5 and 6 above. This completes the gas pressure

setting procedure. Dip switches #7 and #8 (combustion control switches), MUST be returned

to the "Off" position, after setting the pressures.

Refer to page 12 for factory default dip switch settings.