Vi - troubleshooting, Cont.) – LAARS IGE-199C-5(N,X) - Service Manual User Manual

Page 32

Advertising
background image

32

Nature of Fault

Examination

Point

Diagnostic Point

Values

Y/N

Action

Service

Procedure

C. Combustion

occurs, but flame

fails.

Error code "12"

displayed on

digital monitor.

1. Check flame rod.

2. Check ground

wire.

1. Measure the voltage

between flame rod

terminal C

1

and

appliance ground.

2. Check to ensure flame
rod bracket is not loose.

Check for faulty ground

wire connections at unit,

receptacle, and ground

rod to home, and for

broken or shorted wires.

5 ~ 150 VAC

Is it secure?

Are connections

OK?

Yes

No

Yes

No

Yes

No

Go to C-1-2

Replace PCB

Go to C-2

Replace/
rectify

Check for

other causes

of flame

failure.

Replace or

repair

grounding

circuit to unit.

IGE – 2

D. Cannot adjust

water

temperature.

1. Check hot water

thermistor.

(outgoing

thermistor)

# Disconnect connector

B

5

and measure the

resistance between

white ~ white.
(See page 41)

Resistance values

match table on page

#41

Yes

No

Go to D – 2

Replace water

temperature

thermistor.

IGE – 6

2. Check

changeover solenoid

valve (SV3).

1. # Disconnect

connector E from PCB

and measure the

resistance between

brown ~ black.
(See page 39)

2. Measure the voltage

between brown ~ black
wire of the changeover

solenoid valve (SV3) at

connector E.

(See page 39)

1.7 ~ 2.1KΩ

80 ~ 100 VDC

Yes

No

Yes

No

Go to D – 2-2

Replace

manifold

assembly

Go to D – 3

Replace PCB

IGE – 8

IGE – 2

3. Check

modulating valve.

1. # Disconnect

modulating valve at C

2

festoon terminal and

measure resistance at

solenoid terminals.
(See page 42)

2. Measure the voltage

between two harness

terminals at C

2

.

(See page 42)

3. Check whether the

manifold pressure alters

when remote control

temperature is altered

between 96° ~ 140°F.

67 ~ 81Ω

2 ~ 15 VDC

Does the manifold

pressure change?

Yes

No

Yes

No

Yes

No

Go to D – 3-2

replace gas

valve

Go to D – 3-3

Replace PCB

Go to D – 4

Replace gas

valve

IGE – 9

IGE – 2

IGE – 9

4. Check water flow

servo.

1, # Measure resistance

between red ~ blue
wires of the water flow

servo connector B

2

.

(See page 42)

22 ~ 26Ω

Yes

No

Go to D – 4-2

Replace water

flow servo

sensor.

IGE – 3

VI - TROUBLESHOOTING

(cont.)

Troubleshooting Flow Chart

BEFORE CARRYING OUT CHECKS MARKED WITH

A # SIGN, DISCONNECT THE POWER SUPPLY.

Advertising
This manual is related to the following products: