IGE - 11. Removal of Thermal Fuse:

CAUTION

120 volt potential exposure. Isolate the appliance

and reconfirm power has been disconnected

using a multimeter.

This process may involve removing the heat

exchanger if the thermo-fuse on the rear of the

heat exchanger is blown.

(Service Procedure IGE-10, page 50)

a.

The unit has four thermal fuses, see

picture below for location.

b.

Disconnect and remove the thermal fuse.

Re-install new thermo fuse using the

existing thermo fuse clips. Reconfirm inlet

and manifold gas pressures are set to

the proper setting. Ensure unit matches

gas type being supplied to the heater.