8.

Turn off the gas to the water heater. Remove the manometer connection. Reinstall the

pressure port plug. Turn on the gas to the water heater and check for gas leaks around

test port with a leak solution.

9.

Reinstall the front cover and place the unit back into operation.

10.

Verify the proper water temperature, as set on the controller at your outlets. If controllers are

not being used the output temperature should be 120°F, for residential models or 140˚ for

commercial models.

WARNING

Dip switched #7 and #8 (combustion control switches) MUST

be returned to the "OFF" position, after setting pressures.

Figure #1