LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 111

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 107

Code Description

L or

H

Procedure

164

Block intake ON

L

1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it

is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the

voltage across the switch. Supply voltage should

be present. If not, the Block Intake Switch is

defective and needs replacing.
5. If the fault persists, replace the relay module.

165

Block intake OFF

L

1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it

is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the

voltage across the switch. Supply voltage should

be present. If not, the Block Intake Switch is

defective and needs replacing.
5. If the fault persists, replace the relay module.

172

Main relay feedback incorrect

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

174

Safety relay feedback incorrect

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

175

Safety relay open

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

176

Main relay ON at safe start check

L

Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.

178

Safety relay ON at safe start check

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

184

Invalid BLOWER/ HSI output setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

185

Invalid Delta T limit enable setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

186

Invalid Delta T limit response setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.